The following illustration shows basic application of this inverter. It also includes following devices to have a Complete running system. – Generator or Utility – PV modules Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor type appliances such as refrigerator and air conditioner.

 
KEY PRODUCT FEATURES​
TECHNICAL PARAMETERS
Technical ParameterSUN2000-5KTL-M1SUN2000-6KTL-M1SUN2000-8KTL-M1SUN2000-10KTL-M1SUN2000-12KTL-M1
Effectiveness
Maximum efficiency98.40%98.60%98.60%98.60%98.60%
European efficiency97.50%97.70%98.00%98.10%98.20%
Input (inverter)
Maximum recommended component power 17500 Wp9000 Wp12000 Wp15000 Wp18000 Wp
Maximum DC input voltage 21100 V
MPPT voltage range 3140 V ~ 980 V
Starting voltage200 V
Rated input voltage600 V
Maximum input current of each MPPT11:00 AM
Maximum short circuit current15 A
Number of MPPT2
Maximum number of input channels2
Input (energy storage battery)
Adapted energy storage systemHuawei Smart String Energy Storage System 5kWh-30kWh
Operating voltage range600 V ~ 980 V
Maximum working current16A
Maximum charging power10000 W
Maximum discharge power5500 W6600 W8800 W10000 W10000 W
Output
Adapter gridThree phase
Rated output power5000 W6000 W8000 W10000 W12000 W
Maximum output apparent power5500 VA6600 VA8800 VA11000 VA12000 VA
Rated output voltage220 Vac/ 380 Vac, 230 Vac/ 400 Vac, 3W / N+PE
Output voltage frequency50 Hz / 60 Hz
Maximum output current8.5A10.1A13.5A16.9A18.4A
Power factor0.8 leading… 0.8 lagging
Maximum total harmonic distortion≤3 %
Off-grid power outputYes (via Backup Box-B1 4)
Output (Off-grid box Backup Box-B1)
Maximum output apparent power3300 VA
Rated output voltage220 V / 230 V
Maximum output current15 A
Power factor0.8 leading… 0.8 lagging
Protection & Features
Input DC switchYes
Anti-islanding protectionYes
Input reverse protectionYes
Insulation resistance detectionYes
DC surge protectionYes, equivalent to TYPE II protection level in EN/IEC 61643-11
AC surge protectionYes, equivalent to TYPE II protection level in EN/IEC 61643-11
Residual current detectionYes
AC overcurrent protectionYes
AC short circuit protectionYes
AC overvoltage protectionYes
AFCI DC arc protectionYes
Dry node remote schedulingYes
Built-in PID repair 4Yes
Grid AC reverse chargingYes
General parameters
Operating temperature-25 ~ + 60 °C (5-10KTL model derating above 45℃ under rated load, 12KTL model derating above 40℃ under rated load)
Relative humidity0 %RH~100%RH
Working altitude0 ~4000 m (derating above 2000 m)
Cooling methodNatural convection
DisplayLED indicator; built-in WLAN + FusionSolar APP
External communication can be expandedOptional: 4G Standard: RS485
Optional: 4G smart communication stick WLAN-FE smart communication stick
Weight (including mounting parts)17 kg
Dimensions (including mounting parts) (width x height x thickness)525 x 470 x 166 mm
Protection levelIP65
Matching optimizer
Adaptation optimizer modelSUN2000-450W-P
Standards met
SafetyEN/IEC 62109-1, EN/IEC 62109-2
Grid-connected standardNB/T 32004