KERNEL PARAMERERS
BASIC SYSTEM ARCHITECTURE​

The following illustration shows basic application of this inverter. It also includes following devices to have a Complete running system. – Generator or Utility – PV modules Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor type appliances such as refrigerator and air conditioner.

KEY PRODUCT FEATURES​
TECHNICAL PARAMETERS
ModelSUN-10K-SG01HP3-EU-AM2SUN-12K-SG01HP3-EU-AM2SUN-15K-SG01HP3-EU-AM2
Battery Input Data
Battery TypeLithium-ion
Battery Voltage Range (V)160-700
Max. Charging Current (A)37A37A37A
Max. Discharging Current (A)37A37A37A
Number of Battery Input1
Charging Strategy for Li-Ion BatterySelf-adaption to BMS
PV String Input Data
Max. DC Input Power (W)13000W15600W19500W
Max. DC Input Voltage (V)1000V
Start-up Voltage (V)180V
Full Load DC Voltage Range (V)325-850340-850420-850
Rated DC Input Voltage (V)600V600V600V
PV Input Current (A)20+2026+2026+20
Max. PV I (A)30+3039+3039+30
No.of MPPT Trackers2
No.of Strings Per MPPT Tracke1+12+12+1
AC Output Data
Rated AC Output and UPS Power (W)10000W12000W15000W
Max. AC Output Power (W)11000W13200W16500W
AC Output Rated Current (A)15.2/14.518.2/17.422.8/21.8
Max. AC Output Rated Current (A)16.7/1620/19.225/24
Max. Three-phase Unbalanced Output Current(A)22A25A30A
Max. Continuous AC Passthrough (A)40A80A80A
Peak Power (off grid)1.5 time of rated power, 10 S
Generator Input/Smart Load/AC Couple Current (A)15.2/40/15.218.2/80/18.222.8/80/22.8
Power Factor0.8 leading to 0.8 lagging
Output Frequency and Voltage50/60Hz; 3L/N/PE 220/380, 230/400Vac
Grid TypeThree Phase
Total Harmonic Distortion (THD)<3% (of nominal power)
DC Current Injection<0.5% In
Efficiency
Max. Efficiency97.60%
Euro Efficiency97.00%
MPPT Efficiency99.90%
Protection
PV Input Lightning ProtectionIntegrated
Anti-islanding ProtectionIntegrated
PV String Input Reverse Polarity ProtectionIntegrated
Insulation Resistor DetectionIntegrated
Residual Current Monitoring UnitIntegrated
Output Over Current ProtectionIntegrated
Output Shorted ProtectionIntegrated
Output Over Voltage ProtectionIntegrated
Surge protectionDC Type II / AC Type II
Certifications and Standards
Grid RegulationVDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1,
G98, G99, C10-11, UNE217002, NBR16149/NBR16150
Safety EMC / StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
General Data
Operating Temperature Range (℃)-40-60℃, >45℃ Derating
CoolingSmart cooling
Noise (dB)≤55 dB
Communication with BMSRS485; CAN
Weight (kg)30.5
Size (mm)408×638×237 (Excluding Connectors and Brackets)
Protection DegreeIP65
Installation StyleWall-mounted
Warranty5 Years (10 Years Optional)

CONTACT US

Fill out the form below, and we will be in touch shortly.