KERNEL PARAMERERS
BASIC SYSTEM ARCHITECTURE​

The following illustration shows basic application of this inverter. It also includes following devices to have a Complete running system – Generator or Utility – PV modules Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor type appliances such as refrigerator and air conditioner.

KEY PRODUCT FEATURES​
TECHNICAL PARAMETERS
ModelSUN-30K-SG01HP3-EU-BM3SUN-40K-SG01HP3-EU-BM4SUN-50K-SG01HP3-EU-BM4
Battery Input Data
Battery TypeLithium-ion
Battery Voltage Range(V)160~800
Max. Charging Current (A)50+50
Max. Discharging Current (A)50+50
Number of battery input2
Charging Strategy for Li-Ion BatterySelf-adaption to BMS
PV String Input Data
Max. DC Input Power (W)390005200065000
Max. DC Input Voltage (V)1000
Start-up Voltage (V)180
MPPT Range (V)150-850
Full Load DC Voltage Range (V)360-850360-850450-850
Rated DC Input Voltage (V)600
PV Input Current (A)36+36+3636+36+3636+36+36+36
Max. PV ISC (A)55+55+5550+50+5050+50+50+50
Number of MPPT / Strings per MPPT3/24/24/2
AC Output Data
Rated AC Output and UPS Power (W)300004000050000
Max. AC Output Power (W)330004400055000
AC Output Rated Current (A)45.5/43.560.7/5875.8/72.5
Max. AC Output Rated Current (A)50/47.866.7/63.883.4/79.7
Max. Three-phase Unbalanced Output Current607083.3
Max. Continuous AC Passthrough (A)200
Peak Power (off grid)1.5 time of rated power, 10 S
Generator input/Smart load/AC couple current (A)45.5 / 200 / 45.560.7 / 200 / 60.775.8 / 200 / 75.8
Power Factor0.8 leading to 0.8 lagging
Output Frequency and Voltage50/60Hz; 3L/N/PE 220/380, 230/400Vac
Grid TypeThree Phase
Total Harmonic Distortion (THD)<3% (of nominal power)
DC current injection<0.5% In
Efficiency
Max. Efficiency97.60%
Euro Efficiency97.00%
MPPT Efficiency99.90%
Protection
IntegratedPV Input Lightning Protection, Anti-islanding Protection, PV String Input Reverse Polarity Protection,Insulation Resistor
Detection, Residual Current Monitoring Unit, Output Over Current Protection,Output Shorted Protection, Surge protection
Output Over Voltage ProtectionDC Type II/AC Type III
Certififications and Standards
Grid RegulationVDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150
Safety EMC / StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
General Data
Operating Temperature Range (℃)-45-60℃, >45℃ derating
CoolingSmart cooling
Noise (dB)≤65 dB
Communication with BMSRS485; CAN
Weight (kg)75
Size (mm)527W×894H×294D
Protection DegreeIP65
Installation StyleWall-mounted
Warranty5 years

CONTACT US